Cable Distance Calculator
Calculate voltage drop, maximum cable length, and minimum wire gauge for DC, single-phase AC, and three-phase AC circuits. Supports AWG and mm², copper and aluminum, with NEC 3% and 5% voltage-drop limits. Ideal for 12V, 24V, 120V, 240V, and 480V systems.
AWG Wire Resistance & Voltage Drop Reference
Resistance values are approximate and based on NEC Chapter 9, Table 9 (copper, 75°C, PVC conduit). Aluminum resistance is approximately 1.6× copper. Actual values vary with temperature, conduit type, and conductor stranding.
| AWG / kcmil | Area (mm²) | Cu Resistance (Ω/1000 ft) | Al Resistance (Ω/1000 ft) | Typical Ampacity (Cu, 75°C) |
|---|
Why Cable Distance Matters
Every conductor has resistance. As current flows through a cable, some voltage is lost as heat — a phenomenon called voltage drop. The longer the cable and the higher the current, the greater the drop. If the voltage at the load falls too far below the nominal supply, equipment may malfunction, motors may overheat, and lights may flicker.
The maximum cable distance is the length at which voltage drop reaches an acceptable limit. The NEC recommends keeping voltage drop below 3% for branch circuits and 5% for the total feeder-plus-branch run . Many designers use 2% for critical DC systems.
Voltage Drop Formulas
For a DC or single-phase AC circuit (two conductors carrying current in opposite directions):
where I = current (A), L = one-way length (ft), R = resistance (Ω per 1000 ft)
For a three-phase AC circuit:
The percentage voltage drop is simply:
To solve for maximum length, rearrange the formula:
The phase factor is 2 for DC/single-phase and √3 for three-phase.
How Resistance Is Determined
Resistance depends on the conductor material and cross-sectional area. The American Wire Gauge (AWG) system is logarithmic: smaller AWG numbers mean larger conductors and lower resistance. The NEC Chapter 9, Table 9 provides AC resistance values for copper and aluminum conductors at 75°C . Key values include:
- 12 AWG copper: ≈ 1.98 Ω per 1000 ft
- 10 AWG copper: ≈ 1.24 Ω per 1000 ft
- 8 AWG copper: ≈ 0.786 Ω per 1000 ft
- 6 AWG copper: ≈ 0.510 Ω per 1000 ft
Aluminum has about 1.6× the resistance of copper for the same gauge, so it requires a larger conductor to achieve the same voltage drop .
The Three Calculator Modes
- Voltage Drop — given voltage, current, length, gauge, and material, compute the actual voltage drop in volts and percent.
- Maximum Length — given a target voltage-drop percentage, compute the longest run that stays within that limit.
- Minimum Wire Gauge — given a fixed length and allowable drop, compute the smallest AWG that meets the requirement.
Quick rule of thumb for 12V systems: voltage drop is critical. A 10 AWG copper cable carrying 20 A can run roughly 30–40 ft before exceeding a 3% drop. For 120V systems, the same cable can run hundreds of feet.
Why Use This Cable Distance Calculator?
- Three solve modes: Voltage drop, maximum length, and minimum gauge.
- AWG and mm²: Supports both American and metric wire sizes.
- Copper and aluminum: Separate resistance values for both materials.
- DC and AC: Handles DC, single-phase, and three-phase circuits.
- NEC-aligned: Uses Table 9 resistance values and 3%/5% limits.
- Free & private: Runs entirely in your browser — no data is sent to a server.
❓ Cable Distance & Voltage Drop FAQ
What is voltage drop?
Voltage drop is the reduction in voltage along a conductor due to its resistance. It is caused by current flowing through the cable's resistance and is proportional to both current and length. Excessive voltage drop can cause equipment malfunction and energy waste.
What is the maximum allowable voltage drop?
The NEC recommends a maximum of 3% for branch circuits and 5% for the combined feeder and branch circuit. These are informational notes, not strict code requirements, but they are widely adopted as best practice and may be enforced by local authorities .
How do I calculate maximum cable length?
Use the Maximum Length tab. Enter voltage, current, wire gauge, material, and your allowable drop percentage. The calculator rearranges the voltage-drop formula to solve for length: L = Vdrop × 1000 / (phase factor × I × R).
Why does 12V systems need thicker cable?
Because voltage drop is a percentage of the nominal voltage. A 0.5V drop is only 0.4% on a 120V circuit but over 4% on a 12V circuit. To keep the percentage low, 12V systems require much larger conductors for the same current and distance.
Does cable length mean one-way or round-trip?
The formulas use one-way length. The "2" in the single-phase formula accounts for the return path (current flows out and back). For three-phase, the √3 factor accounts for the three conductors.
What is the difference between AWG and kcmil?
AWG (American Wire Gauge) is used for smaller conductors up to about 4/0. Larger conductors are specified in kcmil (thousands of circular mils). For example, 250 kcmil is larger than 4/0 AWG. The calculator supports both.
Does temperature affect voltage drop?
Yes. Conductor resistance increases with temperature. The NEC Table 9 values used here assume 75°C. In hot environments or for conductors operating at higher temperatures, actual resistance and voltage drop will be slightly higher.
Is this calculator free?
Yes. This tool is completely free, requires no registration, and runs entirely in your browser. Your inputs are never sent to a server.